Flow Control Valve
Introduction:
The flow control valve is a multi-functional valve that uses a high-precision pilot method to control the flow. It is suitable for pipelines where the water distribution pipe needs to control the flow and pressure. Keep the predetermined flow unchanged, limit the excessive flow to a predetermined straight line, and appropriately reduce the upstream high pressure. Even if the pressure upstream of the main valve changes, it will not affect the main valve flow downstream of the valve. This valve changes the principle of using an orifice plate or purely mechanically reducing the area of the flow area of the conventional throttle valve, and uses the relevant pilot valve to minimize the loss of capacity during the throttling process. High control sensitivity, safe and reliable, easy to debug and long service life.
Structural Features:
The flow control valve consists of a main valve, a flow regulating valve, a needle valve, a pilot valve, a ball valve, a micro filter and a pressure gauge to form a hydraulic control takeover system. Use hydraulic automatic operation to control and adjust the opening of the main valve, so that the flow through the main valve remains unchanged.
This product uses hydraulic self-control, does not require other devices and energy, is easy to maintain, and has stable flow control. This series of valve products are widely used in high-rise buildings, living areas and other water supply network systems and urban water supply projects.
Working Principle:
When the valve feeds water from the inlet, the water flows through the needle valve into the main valve control room, and flows out of the main valve control room through the pilot valve and the ball valve to the outlet. At this time, the main valve is in a fully open or floating state. By setting the flow regulating valve on the upper part of the main valve, a certain opening degree of the main valve can be set. Adjusting the opening of the needle valve and adjusting the spring pressure of the pilot valve can keep the opening of the main valve at the set opening, and the pilot valve will automatically adjust when the pressure changes to keep the flow unchanged.
Outline Drawing:
Product Showing: